Product Overview
Suitable Applications: | This Category 5e Cable is a cable standard for Gigabit Ethernet, capable to continue transmitting data even when being directly attacked by fire. |
Construction Details
Size | Stranding | Stranding Class | Material | No. of Pairs | No. of Elements |
---|---|---|---|---|---|
22 AWG | Solid | Class 1 | BC – Bare Copper | 4 | 8 |
Material | Nom. Insulation Diameter | Color Code | Notes |
---|---|---|---|
PE – Polyethylene | 1.03 mm (0.0406 in) | Blue & White with Blue Strips, Orange & White with Orange Strips, Green & White with Green Strips, Brown & White with Brown Strips | Fire Protection Barrier: Mica glass Tape(MGT) |
Notes |
---|
All 4 Pairs laid up together over a cross filler & binded by Fire Protection Barrier: Mica Glass Tape(MGT) |
Material |
---|
LSZH – Low Smoke Zero Halogen (Flame Retardant) |
Overall Cable Diameter (Nominal): | 9.60 mm (0.378 in) |
Electrical Characteristics
Max. Conductor DCR | Nom. Characteristic Impedance |
---|---|
54.3 Ohm/km @ 20 Deg. C | 100 Ohm |
Max. Delay Skew |
---|
45 ns/100m |
536 ns/100m |
Frequency [MHz] | Max. Insertion Loss (Attenuation) | Min. NEXT [dB] | Min. PSNEXT [dB] | Min. RL (Return Loss) [dB] |
---|---|---|---|---|
1 | 2.04 dB/70m | 65.3 | 62.3 | 20 |
4 | 4.05 dB/70m | 56.3 | 53.3 | 23 |
8 | 5.77 dB/70m | 51.8 | 48.8 | 24.5 |
10 | 6.47 dB/70m | 50.3 | 47.3 | 25 |
16 | 8.25 dB/70m | 47.2 | 44.2 | 25 |
20 | 9.27 dB/70m | 45.8 | 42.8 | 25 |
25 | 10.42 dB/70m | 44.3 | 41.3 | 24.3 |
31.25 | 11.72 dB/70m | 42.9 | 39.9 | 23.6 |
62.5 | 16.99 dB/70m | 38.4 | 35.4 | 21.5 |
100 | 21.98 dB/70m | 35.3 | 32.3 | 20.1 |
Voltage Rating |
---|
60 V |
Mechanical Characteristics
Operating |
---|
-40°C to + 60°C |
Standards and Compliance
Environmental Suitability: | UV Resistance, Oil Resistance |
Flammability / Reaction to Fire: | IEC 60332-1-2, IEC 60332-3-22, IEC 60331-23, BS EN 50200 PH120 |
AWM Compliance: | AWM 21130 |
Data Category: | Category 5e |
TIA/EIA Compliance: | EIA/TIA 568 |
ISO/IEC Compliance: | IEC 61034-2 – Smoke Density Min Transmittance = 60% |
European Halogen Free Standards: | IEC 60754-1 – Halogen Amount = 0.5 %, IEC 60754-2 – Halogen Acid Gas Amount – Max. Conductivity = 10 µS/mm, IEC 60754-2 – Halogen Acid Gas Amount – Min. pH = 4.3 |
Other Standard Compliance(s): | BS EN 50289-4-16 |
Product Notes
Notes: | TIA 568 D .2 Cat.5E and ISO/IEC 11801 class D and IEEE 802.3 100Base TX,1000Base T, Circuit integrity performance during a fire of the relevant requirements of IEC 60331 23. Cable will meet CAT 5e channel requirements up to 80m length or up to 70m permanent length. |
History
Update and Revision: | Revision Number: 0.17 Revision Date: 01-25-2024 |